What is the role of the copper foil laid under the anti-static floor
When installing the anti-static floor in the computer room, there is a requirement to lay copper foil first. What role does copper foil play in anti-static floor laying?
Anti-static floor is also called conductive floor. The static electricity and charged particles formed by friction in the computer room will attract dust in the air, causing corresponding interference and physical damage to computer rooms, electronics factories and other departments. The conductive floor is the floor is conductive, the floor has conductive fibers, and a layer of copper foil needs to be laid before the anti-static floor is constructed. The anti-static floor is laid with conductive glue.
Copper foil has good conductivity and electrostatic discharge in the computer room, and is used as a conductive material in the computer room
The copper foil is usually laid at 0.05mm, and the specification of 10mm*50m is the best. If the copper foil is too thin, it is easy to break during construction. If it is too thick, more paint will be needed to level the copper foil. The well-shaped pavement is adopted, and the interval can be determined according to the actual situation. After the copper foil paving is completed, install more than two grounding ports in an area of 600 square meters, and weld between the copper wire and the copper foil, so that static electricity can enter the outdoors smoothly. Attention should be paid to the details during the construction process, and the details determine the quality.